Delta Panels Pty Ltd Delta Panels - Panel testing to FP1.4 and 4284 Test Report AS_NZS 4284 30B-20-0134-TRP-16554-0 30 July 2021 Page 7 of 11 Cyclic water test Table 5: Cyclic water test pressure conditions Stage Lower pressure Upper pressure Cycle Duration Stage 1 0.245 kPa 0.490 kPa 5 minutes 0 kPa 2 minutes Stage 2 0.327 kPa 0.654 kPa 5 minutes 0 kPa 2 minutes Stage 3 0.490 kPa 0.980 kPa 5 minutes Observation 0 kPa 5 minutes Water spray For the static and cyclic water tests the water was plied at the following rates during spray operation; 3.0 L/min/m2 applied over 12.48m2 = 37.4L/min. Results: The SLS pressure was achieved and maintained successfully, no water leaks were present during the static and cyclic water pressure tests. Conclusion: The sample complied with the requirements of Clause 8.2 of AS/NZS 4284:2008.