Delta Panels Pty Ltd 
Delta Panels - Panel testing to FP1.4 and 4284 
Test Report AS_NZS 4284 
 
 
30B-20-0134-TRP-16554-0 
30 July 2021 
Page 6 of 11 
 
5 Test Equipment 
Table 4: Test Equipment 
Measurement 
Instrument/Make 
Model 
Asset ID 
Distance 
Tape Measure 
8m 
000033666 
Pressure 
Manometer – PCE 
PDA-10L 
000033540 
Pressure 
Manometer – TEC 
DG-700 
000033498 
Water flow rate 
Flow Meter – Siemens 
MAG6000 
000031229 
Air Flow Rate 
Calibrated fan - TEC 
Duct Blaster 
000033497 
Time 
Stopwatch 
Y1299 
000033567 
 
6 Test Results 
6.1 Clause 8.2 – Preliminary tests 
Test Standard:  
AS/NZS 4284:2008 – Testing of Building Facades 
Test Date: 
 
02/06/2021 
Criteria: 
Static Pressure - Test sample shall withstand the Serviceability Limit State pressure with no 
structural damage or distortion. 
Water tests - Under static and cyclic water tests there shall be no leaks. A leak is considered 
to occur when one or more of the following occur: 
a) 
Water appears on any inside surface of the façade, visible from an occupied space. 
b) 
Uncontrolled water appears on any inside surface of the façade (uncontrolled water is 
defined as any leakage not contained and drained away after 5 minutes). 
c) 
Water appears that is likely to wet insulation, fixtures and finishes. 
d) 
Water appears in other locations specified as unacceptable by the Specifier 
Applied Load: 
 
Static Pressure 
1.63kPa, -2.45kPa  
Duration: 10s 
Static water test  
0.49 kPa 
Duration: water spray operated for 5 minutes at 0 kPa chamber pressure, followed by water 
spray and pressure at the test pressure for 15 minutes. Observe for 5 minutes after removal of 
both water and air pressure. 
Water spray:  
3.0 L/min/m2 
 
 
37.5 L/min 
 
 