DeltaDualCore™ Panel Awning Systems 
 
Revision 1-12 
44 
 
 
Figure 5-4. Model 2: Model geometry for a DeltaDualCore™ roof (equivalent dimensions to DtS 
base case) located directly adjacent to the site boundary. 
 
 
Figure 5-5. Model 3: Sensitivity Study - Model geometry for a DeltaDualCore™ roof assessing 
impact of awning width on heat transfer to the site boundary. 
 
B.3 Design Fire 
The design fire is taken as the combined fire load of an EPS core sandwich panel roof system and Design 
Fire 1 in accordance with Section 4.7.1.1. 
For the EPS core roof system, a heat release rate per unit area (HRRPUA) of 332 kW/m2 is adopted which 
has been derived from bench-scale fire testing that was conducted by the University of Queensland and is 
FRONT VIEW 
SIDE VIEW 
6 m 
2.95 m 
4.9 m 
4 m 
2.7 m 
5 m 
6 m 
Upper surface of roof is 
a burner with constant 
HRRPUA of 332 kW/m2 
Site boundary 
10MW Peak HRR 
fire 
A 
B 
D 
C 
FRONT VIEW 
SIDE VIEW 
6 m 
2.95 m 
4.9 m 
8 m 
2.7 m 
5 m 
10 m 
Upper surface of roof is 
a burner with constant 
HRRPUA of 332 kW/m2 
Site boundary 
10MW Peak HRR 
fire 
A 
B 
D 
C 
SENSITIVITY CASE: 
WIDTH OF AWNING INCREASED BY 100% 