DeltaDualCore™ Panel Awning Systems 
 
Revision 1-12 
43 
 
Appendix B 
  FDS Assessment 
B.1 Introduction 
An FDS analysis is undertaken to assess the combined heat transfer to the site boundary for the 
DeltaDualCore™ system when compared to the DtS base case. 
B.2 Model Geometry 
The model geometries for each of the three FDS models use are described in Figure 5-3, Figure 5-4 and 
Figure 5-5 and include: 
1. 
Model 1: DtS base case. 
2. 
Model 2: DeltaDualCore™ awning with equivalent dimensions to Model 1 (performance solution 
case). 
3. 
Model 3: Sensitivity case where the width of the awning in Model 2 is increased by 100%. 
 
 
Figure 5-3. Model 1: Model geometry for DtS base case. 
 
FRONT VIEW 
SIDE VIEW 
6 m 
2.95 m 
4 m 
4 m 
2.7 m 
5 m 
6 m 
Upper surface of roof is 
a burner with constant 
HRRPUA of 332 kW/m2 
Site boundary 
10MW Peak HRR 
fire 
A 
B 
D 
C 