REPORT NUMBER: ISSUE DATE: PAGE: FR10430-001 ISSUE 2 1 June 2023 14 of 21 THE LEGAL VALIDITY OF THIS REPORT CAN ONLY BE CLAIMED ON PRESENTATION OF THE COMPLETE SIGNED PAPER REPORT. EXTRACTS OR ABRIDGMENTS OF THIS REPORT SHALL NOT BE PUBLISHED WITHOUT PERMISSION FROM BRANZ LTD. branz.nz | 1222 Moonshine Rd, RD1, Porirua 5381, Private Bag 50 908, Porirua 5240, New Zealand ǀ Phone +64 4237 1170 ǀ branz@branz.co.nz Figure 5: Thermocouple Locations and Deflection Points 3.4 Insulation The maximum temperature rise measured on the unexposed face of the wall exceeded the maximum Insulation failure criteria of 180 K after 72 minutes into test. The failure was measured using the roving thermocouple adjacent to a panel joint. Graphs of the mean and maximum temperature rise of the unexposed face of the wall are shown in Figure 6 and Figure 7.