REPORT NUMBER: 
ISSUE DATE: 
PAGE: 
FR10430-001 ISSUE 2 
1 June 2023 
12 of 21 
THE LEGAL VALIDITY OF THIS REPORT CAN ONLY BE CLAIMED ON PRESENTATION OF THE COMPLETE SIGNED PAPER REPORT.  
EXTRACTS OR ABRIDGMENTS OF THIS REPORT SHALL NOT BE PUBLISHED WITHOUT PERMISSION FROM BRANZ LTD. 
 branz.nz | 1222 Moonshine Rd, RD1, Porirua 5381, Private Bag 50 908, Porirua 5240, New Zealand ǀ Phone +64 4237 1170 ǀ branz@branz.co.nz 
3.2.2 
Furnace Control 
The percentage deviation of the area of the furnace mean temperature from the standard 
temperature/time curve was within the standard requirements. 
Figure 3 shows the percentage deviation of the mean furnace temperature from the Standard 
curve. 
Figure 3: Percentage Deviation from Standard Curve 
 
3.2.3 
Pressure Measurements 
The differential pressure of the furnace above the laboratory atmosphere was controlled to be 
0 Pa at 500 mm above the notional floor which corresponds to 3.2 Pa at the pressure probe 
in the furnace. The differential pressure was monitored using a micromanometer connected 
to a computer controlled data logging system which recorded the pressure at 15 second 
intervals.  
Figure 4 shows the furnace pressure variation with time. 
 
 
 
 
 
 
-20
-15
-10
-5
0
5
10
15
20
0
20
40
60
80
100
120
140
% 
Time (minutes)
Actual
Allowable