E: info@deltapanels.com W: www.deltapanels.com Head Office: 731 Boundary Road, Richlands, Qld 4077 | +61 7 3271 2170 Sydney Depot: 11 The Old Northern Road, Narellan, NSW 2567 | +61 2 4611 7712 17 Delta Panels Pty Ltd ABN: 11 147 861 292 DELTA PATIO & ROOFING RANGE Limits For Using Type 1P Awning Classification Following are the dimensional requirements for using Type 1P awning classification, which has 1 partial wall. • For awning dimensions, refer to figure 1. • Awning is to be attached one side only to an existing building. • Awning pitch “α” is to be between 1˚ and 10˚. • Slope of the awning is to be normal to the attached wall. • Minimum hc = 0.05 x d • Maximum hc = 1.0 x d • Maximum hc/wc to be as per Table 1. • Maximum blockage under the roof parallel to the attached wall is to be 56% of the projected area. • Awnings attached one side that do not comply with the above are to be classified as Type 1. Allowable Span (mm) for Delta Beams - Roof panel span of 6.5m with 1m overhang Wind Class N2 N3 N4 N5 100x1.0 Beam 3620 2820 2970 2300 150x1.2 Beam 4770 3640 3850 2920 200x1.2 Beam 5500 4110 4370 3220 250x1.6 Beam 7960 6500 6780 5270 300x1.6 Beam 8630 7000 7380 5490 Allowable Span (mm) for 0.48 BMT Delta Single in non-cyclonic regions Wind Class Single-Span Multi-Span Cp,n Cp,n 0.5 0.7 1 1.2 0.5 0.7 1 1.2 Patio Type 1P 1 2+4 3 1P 1 2+4 3 N1 5340 5130 4550 4280 6330 5820 4820 4370 N2 5240 4910 4060 3650 5850 4900 4050 3650 N3 4630 3850 3130 2820 4620 3850 3130 2820 N4 3720 3060 2500 2250 3710 3060 2490 2250 N5 2970 2460 2010 1830 2970 2450 2010 1830 DeltaSingleTM 1. Minimum roofing slope to be 1˚. 2. The minimum fixing requirements are 3/14g screws per sheet per support. 3. Allowable deflection limit for wind loading is span / 50. 4. Maintenance load of 0.5kN has been allowed for. 5. DeltaSingleTM is classified as a non-trafficable roof. 6. Maximum allowable overhang of sheeting is 30% of the adjacent span or 900mm, whichever is lesser. 7. ‘Roof Span’ is the maximum spacing of supports for sheeting. 8. Design wind class is to be determined in accordance with AS 4055:2021, Wind Loads for Housing. 9. The structural adequacy to any existing structure to which the sheeting and/or beam is to attached, must be checked by an Engineer. 10. Any side of new roofing with more than 50% clear area of ground to sheeting blocked, is considered to be an enclosed wall.
View this content as a flipbook by clicking here.