Delta MW and EPS-FR Panel Awning and Patio Roof System Revision 1-4 40 Appendix B FDS Assessment B.1 Introduction An FDS analysis is undertaken to assess the combined heat transfer to the site boundary for the Delta MW and EPS-FR roof system when compared to the DtS base case. B.2 Model Geometry The model geometries for each of the three FDS models use are described in Figure 5-3, Figure 5-4 and Figure 5-5 and include: 1. Model 1: DtS base case. 2. Model 2: Delta MW and EPS-FR roof system with equivalent dimensions to Model 1 (performance solution case). 3. Model 3: Sensitivity case where the width of the awning in Model 2 is increased by 100%. Figure 5-3. Model 1: Model geometry for DtS base case. FRONT VIEW SIDE VIEW 6 m 2.95 m 4 m 4 m 2.7 m 5 m 6 m Upper surface of roof is a burner with constant HRRPUA of 332 kW/m2 Site boundary 10MW Peak HRR fire A B D C