FSZ 2373 | page 12 of 38 8.4 Performance Performance observed in respect of Clause 14.4 of AS 1530.8.1-2018 criteria: Performance Criteria Time to failure (min) Position of failure A gap from the fire exposed face to the non-fire exposed face greater than 3-mm No Failure - Sustained flaming for 10 seconds on the non-fire side No failure - Flaming on the fire-exposed side at the end of the 60 minutes test period No failure - Radiant heat flux 365-mm from the non-fire side exceeding 15-kW/m² Not Applicable - Mean and maximum temperature rises greater than 140 K and 180 K No failure - Radiant heat flux 250-mm from the specimen, greater than 3-kW/m² between 20 minutes and 60 minutes No failure - Mean and maximum temperature of internal faces exceeding 250°C and 300°C respectively between 20 minutes and 60 minutes after the commencement of the test Not Applicable - Crib class AA Peak heat flux 29 kW/m² For the purpose of building regulations in Australia, the test specimen achieved a Bushfire Attack Level (BAL) of AA29. This report details the methods of construction, the test conditions and the results obtained when the specific element of construction described herein was tested in accordance with the test method of AS 1530.8.1. 9 Tested by Chris Wojcik Testing Officer