FSZ 2373 | page 11 of 38 20 minutes - Pilot flame was applied over the exposed face of the specimen – no ignition was noted at this time. 3-mm gap gauge applied to the specimen – No through gaps were noted. 58 minutes - Pilot flame was applied over the exposed face of the specimen – no ignition was noted at this time. 61 minutes - Test terminated. Post Test Inspection 3-mm gap gauge applied to the specimen – no through gaps were noted. 8.2 Radiant heat flux Figure 1 shows the curves of target and incident radiation versus time recorded during the test period. Figure 2 shows the curve of received radiation versus time at 250-mm from the exposed face of the specimen. 8.3 Specimen temperature Figure 3 shows the temperature versus time recorded on the unexposed face of the wall. Figure 4 shows the temperature versus time associated with crib 1. Figure 5 shows the temperature versus time associated with crib 2. Figure 6 shows the temperature versus time associated with crib 3. Figure 7 shows the temperature versus time associated with the eave.