Fire Engineering Assessment, Revision 01 
DeltaCool, DeltaSecrectFix, DeltaTrim at 100 mm and 75 mm Fire Performance, Project No. 25367 
25367-SFE-FEA-01-Delta Panel Fire Performance 
 
 
Page 16 
4.1 
FIRE PERFORMANCE OF DELTASECRETFIX, DELTATRIM, DELTACOOL 
4.1.1 Introduction 
The following assessment addresses Departure Item 1 identified in Table 1-1. 
Item 
Parameter 
Fire Engineering 
Assessment Description  
DeltaCool™ 100 mm thick smooth panel with a mineral wool core was tested in 
accordance with AS ISO 9705:2003(R2016) and classified against AS 
5637.1:2015. The reaction to fire test report, RTF252619 R1.0 by Jensen Hughes, 
indicated that the DeltaCool™ 100 mm thick panel achieved a Group Number of 
1. 
It is proposed to utilise the test report for the DeltaCool™ 100 mm thick panel to 
indicate the fire performance of the following panels: 
- 
DeltaCool™ 75 mm thick panel with a mineral wool core 
- 
DeltaSecretFix™ 100 mm thick panel with a mineral wool core 
- 
DeltaSecretFix™ 75 mm thick panel with a mineral wool core 
- 
DeltaTrim™ 100 mm thick panel with a mineral wool core 
- 
DeltaTrim™ 75 mm thick panel with a mineral wool core 
NCC DtS Clause(s) 
C2D11, S7C4 
NCC Clause A2G2(3) – 
Performance 
Requirements 
C1P2, C1P4, C1P9 
NCC Clause A2G2(1) – 
Solution Compliance 
(a) 
NCC Clause A2G2(2) – 
Assessment Method 
(b)(ii) 
Analysis Methodology 
 Comparative 
 Qualitative 
  
 Deterministic 
 Absolute 
 Quantitative 
 
 Probabilistic 
Acceptance Criteria 
Acceptance is taken as that each component of the panel does not significantly 
contribute the fire hazard above what is tested in the reaction to fire test 
report by Jensen Hughes. 
 
4.1.2 Specific Hazards 
The specific hazards identified due to the non-compliance: 
1. The panels have not been tested to confirm whether it achieves a Group Number of 1 in accordance 
with AS 5637.1-2015 in the absence of testing to AS ISO 9705:2003(R2016). Thus, the contribution  to 
the fire hazard of the panels is unknown and the panels may have an unknown impact on occupants 
tenability or obstruction. 
4.1.3 Relevant Fire Engineering Systems to Address the Hazard 
As part of the Fire Engineering Assessment, the following is proposed: 
- 
75 mm thick DeltaCool™ panel, 100 mm DeltaSecretFix™ panel, 75 mm DeltaSecretFix™ panel, 100 
mm DeltaTrim™ panel, and 75 mm DeltaTrim™ panel is expected to achieve a Group Number of 1 if 
tested to AS ISO 9705:2003(R2016) and classified against AS 5637.1:2015 on the condition that : 