Fire assessment report R1.0 
Page 21 of 21 
Copyright ©2025 Jensen Hughes, Inc.  
 
All Rights Reserved. T1124 PAC 
Appendix C Summary of supporting test data 
C.1 
Test report – RTF252619 R1.0 
Table 8 Information about test report 
Item 
Information about test report 
Report sponsor 
Delta Panels Pty Ltd, 731 Boundary Road, Richlands QLD 4077, Australia 
Test laboratory 
Jensen Hughes Fire Testing, 409-411 Hammond Road, Dandenong, Victoria 3175, 
Australia. 
Test date 
The reaction to fire test was done on 22 October 2025. 
Test standards 
The test was done in accordance with AS ISO 9705:2003 (R2016).  
Variation to test standards 
Smoke obscuration measurements were made using a helium-neon laser smoke 
photometer, as outlined in Annex H of ISO 9705-1:2016 in lieu of a halogen bulb and 
photocell apparatus as outlined under Annex E.4 of AS ISO 9705 (2016). This is not 
expected to prejudice the test outcome.  
General description of tested 
specimen 
The tested panels consisted of a 99 mm thick mineral wool core sandwiched between 
two 0.65 mm thick roll-formed painted steel skins. The panels were joined along the 
vertical joint, where one edge has a tongue, while the other edge has a groove. The 
tongue edge locks into the groove edge of the next panel. 
Instrumentation 
The test report states that the instrumentation was in accordance with 
AS ISO 9705:2003 (R2016). 
The test specimen achieved the following results – see Table 9. 
Table 9 Results summary for this test report  
Criteria 
Results 
Group number 
1 
SMOGRARC (in m2/s2 × 1000) 
1.5 
 