FCO-3545
Page 4 of 16
Copyright CSIRO 2024 This report may only be reproduced in full. Alteration of this report without written authorisation from CSIRO is forbidden.
1 Introduction
This is a report of the bushfire performance of Delta Panel roof systems in accordance with AS 1530.8.1-
2018 up to BAL 29.
This report is prepared for meeting the requirements of AS 3959-2018 clauses 3.4 and 3.8 and NCC 2022
Volume 2 Clause A5G3 1 (d) as appropriate to the required Bushfire Attack Level (BAL) performance.
This report reviews and confirms the extent to which the reference BAL tests listed in section 2 meet
the requirements of the fire test standards listed in section 4 of the report. The proposed variations to
the tested construction presented in Section 3 are subject to an analysis in Appendix B and the
conclusions are presented in Section 5 of this report.
The field of applicability of the results of this assessment report is presented in Section 6 and is subject
to the requirements, validity, and limitations of Sections 7, 8 and 9.
2 Supporting Data
This assessment report refers to various test reports to support the analysis and conclusions of this
report. They are listed below in Table 1.
Table 1: Referenced test data
Report
Reference
Test Standard
Outline of Test Specimen
FSZ 2411
AS 1530.8.1-2018
The specimen comprised a 45-degree pitched Delta Panels roof system that
included a roof valley and a roof ridge detail.
The test report FSZ 2411 was undertaken by CSIRO and sponsored by Delta Panels Pty Ltd.