DeltaCool-MW is an Insulated Wall Panel System,
comprising of two pre-painted, roll-formed steel skins,
bonded to a non-combustible mineral wool core.
Both skins have a roll-formed tongue and groove edge.
Skins are coated with an anti-bacterial paint that inhibits
the growth of bacteria.
Early Fire Hazard Properties AS 1530.3:1999
AWTA Test Report 18-006075 14-11-20181989
Index
Test Range
External Top Skin
Ignitability
0-20
0
Spread of Flame
0-10
0
Heat Evolved
0-10
0
Smoke Developed
0-10
3
Flameguard FRL Systems Vertical Walls
BRANZ Report Number
FR1043-001 30/10/2018
Panel Thickness
100mm
Maximum FRL
-/60/120
Combustibility Test AS 1530.1-1994
CSIRO Report no. FNC12604 dated 8/7/2020 tested five
(5) samples of the Delta Panels supplied mineral wool
sample and certified that the material is NOT deemed
combustible according to the criteria specified in clause
3.4 of AS 1530.1-1994.
Non-Combustibility Building Material - NCC Section C1.9
The Delta Panels laminated mineral wool products are
certified, by Milanovic Neale Consulting Engineers 28/8/2020,
to meet the three performance criteria in the NCC (2019)
Section C1.9 (non-combustible building elements)
Steel Skin Details
ColorBond®
Top Skin
0.60mm / G300 Z275
Bottom Skin
0.60mm / G300 Z275
Max. Skin Temperature
78oC Dry Heat
Core Material Details
Mineral Wool
Thermal Conductivity
0.0365 W/mK @23.0oC
Adhesive
Thermosetting two-part adhesive
Core Density
100kg/m3
Panel Weight (kgs/m2)
based on 0.6mm steel
skins
75mm Panel
18.50
100mm Panel
21.00
125mm Panel
23.50
150mm Panel
26.00
External Wall
R Value (m2.K/W)
AS/NZS 4859 Parts 1 &
2:2018
Thickness
Winter (15o)
Summer (23o)
75mm Panel
2.25
2.15
100mm Panel
2.95
2.85
125mm Panel
3.70
3.55
150mm Panel
4.40
4.20
Sheet Coverage
1200mm
Length (mm)
Cut to Length Min of 1800mm
Length Tolerance (mm)
5mm+/-
Thickness (mm)
75, 100, 125, 150
Flatness
Standards
0.60mm
Surface deformations can be
apparent to the naked eye
when observed in certain
lighting conditions
Detail A
Detail B
SPECIFICATIONS
-MW
-MW
Delta Panels Pty Ltd - ABN: 11 147 861 292
E: info@deltapanels.com
W: www.deltapanels.com
Head Office: 731 Boundary Road, Richlands, Qld 4077 P: +61 7 3271 2170
Sydney Depot: 11 The Old Northern Road, Narellan, NSW 2567 P: +61 2 4611 7712
Version Date: 2025-12-04
Fire Test Certificate - AS ISO 9705
Group 1 Classification in accordance with NCC 2022
Volume One Amendment 2 Clause C2D11 & Clause S7C4
determined in accordance with AS 5637.1:2015 as per
Jensen Hughes test report 252674 issued 28 November
2025 & Spectra Fire Engineers report 25367 issued 25
November 2025