DeltaFireXTM Car Port System 
 
Revision 1-4 
20 
 
(a) Two or more sides (making up at least one third of the awning perimeter) shall be “open” 
in accordance with NCC 9.2.8 (b); that is the roof covering shall be more than 500 mm 
from another building or allotment boundary on at least two sides without enclosing 
these sides with a wall, privacy screen, vehicle access door or the like within 500mm of 
the edge of the roof covering. A boundary along a road or public space such as 
parklands, lakes, rivers and the like (where the construction of buildings is unlikely) may 
be considered open regardless of proximity to the boundary subject to no vertical 
obstruction (wall, privacy screen, vehicle access door or the like) within 500 mm of the 
edge of the roof covering. 
(b) All components used in the awning construction shall be compliant with Section 3. The 
components shall not be modified except with the written authorisation of the 
manufacturer and SOTERA.  
(c) The awning structure shall not provide direct vertical support to any part of the adjacent 
Class 1 building. 
(d) The DeltaFireXTM car port shall consist solely of the following: 
(i) DeltaTrim-MW and DeltaOrb-MW panels 
(ii) Steel fixtures, gutters and the like 
(iii) Steel columns, beams, purlins and the like  
(iv) Metallic flashing 
(e) As the DeltaTrim-MW and DeltaOrb-MW sandwich panels used in the DeltaFireXTM car 
port system constitutes bonded laminates, the following restrictions shall apply to the 
DeltaTrim-MW and DeltaOrb-MW sandwich panels: 
(i) Each lamina shall be non-combustible. For clarity this includes low carbon steel 
(see AS1530.1 test in Section A.2) or mineral wool (see AS1530.1 test in 
Section A.1). As permitted under Section 3.3.2, low carbon steel from any 
manufacturer may be used and the steel may include a surface finish not 
exceeding 1 mm thickness with a spread of flame index no greater than 0. 
(ii) Each adhesive layer may not exceed 1 mm in thickness and the total combined 
thickness of adhesive layers may not exceed 2 mm. 
(iii) The spread of flame index and the smoke developed index of the bonded 
laminated material as a whole shall not exceed 0 and 3 respectively (refer to 
AS1530.3 test certificates given in Section Appendix B).   
4.5 
Methodology 
The method of assessment is qualitative to justify the risk and mitigate the hazard as identified in Sections 
4.2.1 and 4.2.2.  
Performance requirements are addressed comparatively in accordance with BCA A2G2(1)(b) and 
A2G2(2)(d).      
4.6 
Acceptability Criteria 
It shall be demonstrated that the DeltaFireXTM car port system is equivalent to a DtS open car port in 
accordance with NCC Clause 9.2.8. 
4.7 
Assessment 
NCC H3D2 (1)permits that a bonded laminate, although combustible, may be used wherever a non-
combustible materials is required subject to: 

View this content as a flipbook by clicking here.